25.11.2026 by Viktor Siebert
Mitsubishi FR-A520-5.5K-09: FREQROL-A500 inverter repair and troubleshooting
When does the inverter report a fault? At startup, at a steady speed, during deceleration or after it has been running for a while? That detail helps make sense of the alarm on the display. Using a Mitsubishi FREQROL-A500 FR-A520-5.5K-09 from our workshop, we explain what to record before a repair and what we checked afterwards.
What the inverter does
The FREQROL-A500 controls the speed of a three-phase motor by adjusting the voltage and frequency at its output. The inverter first converts the AC supply to DC. Its output stage then uses that DC link to generate a three-phase output for the motor. DC link voltage is therefore a separate item to check alongside power-up behaviour and cooling.
The FR-A520-5.5K-09 shown here belongs to the 200 V class. When specifying a spare, check the full model number, including the -09 suffix, the supply voltage and the parameters used in the machine.
Technical data from the nameplate
| Item | Rating or specification |
|---|
| Manufacturer and series | Mitsubishi Electric, FREQROL-A500 |
|---|
| Model | FR-A520-5.5K-09 |
|---|
| Power | 5.5 kW |
|---|
| AC input | Three-phase, 200 to 220 V AC at 50 Hz or 200 to 240 V AC at 60 Hz |
|---|
| Input current | 35.5 A |
|---|
| Motor output | Three-phase, 200 to 240 V AC as marked on the nameplate |
|---|
| Output current | 24 A |
|---|
| Output frequency | 0.2 to 400 Hz |
|---|
What do FREQROL-A500 alarm codes mean?
These codes come from Mitsubishi Electric’s series manual. The code identifies the protection function that operated. The point in the cycle and the machine’s condition help narrow down the cause.
| Code | Meaning | What to record or check |
|---|
| E.UVT | Undervoltage | Record when the alarm appeared and any preceding supply interruptions. If it recurs, have maintenance personnel check the inverter supply. |
|---|
| E.OC1 | Overcurrent during acceleration | Record whether the motor was under load at startup and whether the acceleration time or load had changed. |
|---|
| E.OC2 | Overcurrent at constant speed | Record changes in load and other machine alarms at the same time. |
|---|
| E.OC3 | Overcurrent during deceleration | Identify the point in the braking cycle when the fault occurred. The motor and cable are part of the same drive system. |
|---|
| E.OV3 | DC link overvoltage during deceleration or stopping | Consider the deceleration ramp and the load. When slowing down, the motor can feed energy back into the DC link. |
|---|
| E.FIN | Heatsink overtemperature | Consider ambient temperature, airflow and any dirt obstructing the heatsink. |
|---|
When the display is on and the motor is stationary
If the control panel lights up, first look at its operating mode and display. In external control mode, the inverter needs a start command and a frequency reference from the machine. Record what the display shows, whether the machine is enabling the drive, and when the motor was expected to start. If the inverter trips, take a photo of the code and record the order of the alarms in its history.
A workshop repair for a customer in Elsoff
A customer in Elsoff, Germany, sent us the Mitsubishi FR-A520-5.5K-09 shown here. We carried out a targeted repair and thoroughly cleaned the unit. We then checked its power-up behaviour, fan operation and the presence of DC link voltage. After we returned the inverter, the customer put it into spare parts stock.
Maintenance and keeping a spare
Keep the airflow paths around the inverter and in the control cabinet clear. For a spare unit, keep the full model number, the machine’s parameter settings and the wiring documentation together. When a fault occurs, record the exact alarm and what the machine was doing just before the trip. Electrical checks and work inside the control cabinet should be carried out by qualified personnel.
Sources
The ratings are taken from the nameplate shown below. The Mitsubishi Electric FREQROL-A500 manual covers operating modes and parameters in chapter 4, protective functions in chapter 5 and maintenance in chapter 6. https://dl.mitsubishielectric.com/dl/fa/document/manual/inv/ib0600133e/ib0600133eb.pdf
Repair and troubleshooting video
Photos before and after repair
Before repair, showing the control panel and fan grille.
After repair, showing the control panel and fan grille.
Before repair, showing the cable entry openings.
After repair, showing the cable entry openings.
Nameplate of the Mitsubishi FR-A520-5.5K-09.
Request a Mitsubishi FREQROL-A500 repair
Send us a photo of the nameplate, the alarm code and a brief description of the fault. If possible, tell us whether it occurs at power-up, on acceleration, while running or during braking.
Industrypart’s Mitsubishi repair service
https://www.industrypart.com/manufacturers/mitsubishi